VFD Pump Control: Savings Depend on the System Curve, and What to Watch on Minimum Speed, Motors and Resonance
A variable frequency drive (VFD) is the most common energy-saving measure on pumping systems, but "slow down and save power" holds only in part of them. How much you save depends mainly on how the system curve splits between static head and friction; the speed floor, motor and bearing capability, resonance and cavitation decide whether it can be used safely. This article compares throttling with VFD control in a reproducible example, then goes through minimum speed, parallel pumps, the effect of drives on motors, and the resonance and cavitation issues across the speed range.
The affinity laws and where they stop
For one pump at changing speed n, similar points satisfy: flow Q ∝ n, head H ∝ n2, shaft power P ∝ n3, with efficiency roughly unchanged. At 80% speed that means 80% flow, 64% head and 51% power.
| Speed ratio n/n0 | Flow ratio | Head ratio | Power ratio |
|---|---|---|---|
| 0.9 | 0.90 | 0.81 | 0.73 |
| 0.8 | 0.80 | 0.64 | 0.51 |
| 0.7 | 0.70 | 0.49 | 0.34 |
| 0.6 | 0.60 | 0.36 | 0.22 |
| 0.5 | 0.50 | 0.25 | 0.13 |
The table describes similar points, not actual operating points. Similar points lie on a parabola through the origin, while a system curve with static head does not pass through the origin, so the operating point does not follow that parabola. The guide "Variable Speed Pumping: A Guide to Successful Applications", written by Europump, the Hydraulic Institute and the US Department of Energy, warns specifically that using the affinity laws to estimate savings in systems with static head is a common mistake: power and energy fall much more slowly with speed there, and VSDs are most effective in high-friction systems. The "efficiency unchanged" assumption also degrades at large speed reductions as leakage and mechanical losses take a bigger share, so use manufacturer data.
The system curve decides the saving: a reproducible example
A system curve can be written Hsys = Hs + kQ2, where Hs is static head and kQ2 is friction and local loss. All numbers below are assumptions for illustration:
- Pump: at full speed H = 40 - 0.00025Q2 (Q in m3/h, H in m); at speed ratio r, H = 40r2 - 0.00025Q2.
- Design point Q = 200 m3/h, H = 30 m. System A: Hs = 10 m, k = 0.0005; system B: Hs = 25 m, k = 0.000125. Both need 30 m at the design point.
- Efficiency at similar points η = 0.80 - 2×10-5(Q - 220)2 (full-speed curve, BEP at 220 m3/h); with a VFD, substitute the similar-point flow Q/r. Shaft power P = 0.002725 × Q × H / η (kW). Drive efficiency 97%, motor efficiency taken as unchanged.
- Required flow drops to 140 m3/h, 70% of design.
| System | Method | Speed ratio | Pump head (m) | Pump efficiency | Shaft power (kW) |
|---|---|---|---|---|---|
| A (static 10 m) | Valve throttling | 1.00 | 35.1 (valve takes 15.3) | 67.2% | 19.93 |
| A | VFD | 0.786 | 19.8 | 76.5% | 9.87 |
| B (static 25 m) | Valve throttling | 1.00 | 35.1 (valve takes 7.65) | 67.2% | 19.93 |
| B | VFD | 0.899 | 27.45 | 71.7% | 14.60 |
Results: shaft power at the design point is 20.64 kW, and throttling to 70% flow only brings it to 19.93 kW, almost no saving. With a VFD, system A cuts shaft power by about 50% (about 49% after drive losses), system B by only about 27% (about 25% after drive losses). The same reduction to 70% flow, with static head going from one third to five sixths of the duty head, halves the saving. Before a VFD retrofit, the first task is not choosing a drive but measuring the system curve: static head, friction share and the time distribution of flow.
Minimum speed and minimum flow
- Static head sets a hard floor: the pump shut-off head 40r2 must exceed the static head for any flow. In the example, system B reaches zero flow at r = √(25/40) ≈ 0.79, and the usable floor is higher still; system A is around 0.5.
- Judge %BEP at the similar point: after slowing down, convert flow to the similar-point flow Q/r before comparing with the BEP. In the example, A has a similar-point flow of 178 m3/h, about 81% of 220; B has 156 m3/h, about 71%. The operating-region concept in ANSI/HI 9.6.3 and the manufacturer's minimum continuous stable flow still apply.
- Motor cooling: a self-ventilated motor moves less air at low speed. Pumps are square-law torque loads, so torque is small at low speed and the issue is milder than with constant-torque loads, but long periods at low speed still need a temperature-rise check with the motor maker. PUMPVIZ Motor Selection and Analysis warns about cooling when the drive output falls below half the base frequency.
- Solids-bearing liquids: too low a speed drops pipe velocity below the settling velocity and solids deposit. Derive the minimum speed from the pipe-velocity check.
- Lubrication and sealing: bearing housings with splash lubrication may be short of oil at low speed, and seal flush arrangements depend on speed, so confirm the minimum permitted speed with the manufacturer.
Parallel pumps with VFDs
In parallel, flows add at the same head: n identical pumps at the same speed deliver Q = n × q. A few rules of thumb:
- Run the pumps at the same speed: at equal speed each pump sits at the same similar point, which spreads efficiency evenly. With one VFD pump and the rest at line speed, the fixed-speed pumps stay at high flow and push the VFD pump to low flow, possibly out of its preferred operating region.
- Set staging points by comparing power: at the target flow compare the total input power of n and n + 1 pumps rather than staging by flow percentage, and keep each pump's similar-point flow above its minimum continuous flow.
- Curves differ between pumps: pumps with different wear states share flow unevenly, so check each unit's performance before applying a drive.
PUMPVIZ Duty Simulation can set 2-8 pumps in series or parallel and drag speed and valve opening to see the combined curve, system intersection, efficiency and power directly.
What a drive does to the motor
- Insulation stress: the fast voltage edges of PWM output, plus reflections on long cables, produce overvoltage at the motor terminals. IEC TS 60034-25 is the application guide for converter-fed motors; IEC 60034-18-41 sets requirements for Type I insulation systems that must not see partial discharge; NEMA MG 1 Part 31 covers definite-purpose inverter-fed motors. Usual practice is to specify an inverter-duty motor, add dv/dt or sine filters where needed and limit cable length, with limits taken from the motor and drive maker.
- Bearing currents: switching creates a common-mode voltage, and when the oil film breaks down the bearing discharges, causing electrical pitting and fluting. Common measures are insulated or hybrid ceramic bearings, shaft grounding brushes, common-mode filters and good earthing.
- Harmonics and extra losses: drive supply increases core and copper loss and raises temperature rise; supply-side harmonics can be limited with line or DC reactors.
- Which efficiency label means what: the IE classes of IEC 60034-30-1 apply to line-operated motors. The drive itself (IE0-IE2) and the motor-plus-drive power drive system (IES classes) are defined in IEC 61800-9-2 (formerly EN 50598-2), and the energy efficiency index of a pump, motor and drive taken as one product belongs to the extended product approach of IEC 61800-9-1. Regulation (EU) 2019/1781 requires drives to reach IE2 but does not make using a drive mandatory.
Cavitation and resonance speeds to avoid
- Cavitation: NPSHr scales roughly with speed squared, so slowing down helps; running above rated frequency does the opposite and NPSHr rises quickly, so check the NPSHr curve and margin first. See Understanding NPSH. NPSHa is set by the installation and does not change with speed.
- Resonance: a VFD sweeps speed through the natural frequencies of pump, piping and foundation, and through blade-pass frequency. An appendix of ANSI/HI 9.6.4 notes that critical speeds should be identified over the operating speed range and either avoided or their effects mitigated. In practice: find resonance bands by bump test or measured vibration, set skip-frequency zones in the drive and pass through them quickly. The price is that steady operation inside a skip zone is impossible, so the control range and saving potential narrow.
- Vertical and submersible pumps: the critical-speed check in PUMPVIZ Filter Search requires the duty speed to sit in the safe zone of the first critical speed (below 0.8 times, or 1.2-1.6 times). With a VFD, check every commonly used speed in the range.
Throttling, bypass, impeller trimming and VFD compared
| Method | Power behaviour | Fit and limits |
|---|---|---|
| Valve throttling | The pump moves left on its own curve; power falls very little (20.64 to 19.93 kW above) and the valve burns the excess head | Lowest investment; long periods at low flow push %BEP down and raise wear and noise |
| Bypass recirculation | The pump still delivers design flow; power barely drops | Only for minimum-flow protection or constant-flow needs, not an energy measure |
| Impeller trimming | A one-off permanent head reduction with a matching power reduction | Suits a lasting oversize; irreversible, and cannot follow varying flow |
| VFD control | The operating point moves down the system curve; saving depends on static-head share and operating hours | Most valuable with varying flow demand; needs minimum speed, motor and resonance issues handled, and carries drive loss (3% in the example) |
To assess the benefit, put the annual flow distribution (a few typical flows and their hours) through the method above point by point, then compare with the investment. Green, Low-Carbon and Efficient Pumps discusses such comparisons from a life-cycle cost angle.
Summary and checklist
- Measure the system curve first: the higher the static-head share, the lower the VFD saving; pure-friction systems benefit most.
- Do not use the affinity laws directly to estimate savings in systems with static head; calculate point by point on the system curve.
- Set the minimum speed from the static-head floor, similar-point %BEP, pipe velocity, motor cooling, lubrication and sealing.
- Run parallel pumps at equal speed and stage them by comparing power.
- For the motor, check insulation class and bearing-current protection, and choose filters and earthing.
- For cavitation, check the NPSHr margin; for resonance, identify bands, set skip zones and assess their effect on savings.
- Base saving and payback estimates on the annual flow distribution, not a single duty point.
References
- Europump, Hydraulic Institute and US Department of Energy, Variable Speed Pumping: A Guide to Successful Applications (Executive Summary)
- ANSI/HI 9.6.3, Rotodynamic Pumps - Guideline for Operating Regions, Hydraulic Institute
- ANSI/HI 9.6.4, Rotodynamic Pumps for Vibration Measurements and Allowable Values, Hydraulic Institute
- IEC TS 60034-25, Rotating electrical machines - AC electrical machines used in power drive systems - Application guide
- IEC 60034-18-41, Qualification and type tests for Type I electrical insulation systems used in rotating electrical machines fed from voltage converters
- NEMA MG 1 Part 31, Definite-Purpose Inverter-Fed Polyphase Motors
- IEC 61800-9-1 / IEC 61800-9-2 (formerly the EN 50598 series), Ecodesign for power drive systems, motor starters, power electronics and their driven applications
- IEC 60034-30-1, Efficiency classes of line operated AC motors (IE code)
- Commission Regulation (EU) 2019/1781, ecodesign requirements for electric motors and variable speed drives